Excess Flow Valves are an additional feature to be used in combination with bursting discs to protect a refrigeration system from overpressure.

EXCESS FLOW VALVES

The use of excess flow valves is recommended in accordance with fact sheet AD2000 A1 and ASME Boiler & Pressure Vessel Code VIII Div.1 (paragraphs UG 125 through UG 137) when bursting discs or relief valves are being used in series or in combination. Excess flow valves keep the space between safety valve and bursting disc pressureless in case smaller leaks occur. They prevent the build-up of counter pressure. They work with a ball that gets pushed into its seat, if an overpressure occurs, e. g. when the bursting disc opens, thus preventing ventilation and enabling the safety valves to perform as intended. Furthermore pressure manometers and controllers can be connected

Excess Flow Valves

Technical Features

  • Available in stainless steel
  • Selection of body material as per German DIN EN12284, AD2000 Series W
  • Working mediums: refrigerants as per EN 378 p. 1, e. g. NH3, R22, R134a; gaseous mediums
  • Use of bursting discs is not permitted in a system where the maximum operating pressure is higher than 90% of the low bursting tolerance. Bursting discs are suitable for gases, but not liquids. The burst tolerance is +/- 10% or optionally +/-5%.
Excess Flow Valves
materialstainless steel
nominal sizeappropriate for bursting discs DN 15-100
nominal pressure levelDN15-25: PS 25, 40, 63
DN 32-100: PS 40
temperature range-60 °C to +150 °C
temperature range for
HT Valve Series
-10 °C to +200 °C
connectionto be connected to the bursting disc holder
via a G1/4″ or NPT1/4″ thread

Downloads

GEA 洞察

Lemgo plant building

将过去与未来融合在莱姆戈的开创性区域供热项目中

Theo van der Zwaag from the Netherlands stands in front of a GEA automated feeding robot.

自动化为奶牛、人类和地球带来改变

CIAL Chile Employees stand in front of a line of defrosters from GEA.

GEA 的解冻解决方案在智利的 CIAL 取得成功

接收 GEA 新闻

订阅 GEA 的新闻,掌握 GEA 的创新信息和故事。

联系我们

我们随时为您提供帮助!您只需提供少量详细信息,我们就能回复您的查询。